久久精品国产欧美日韩,成年女人黄小视频,国产日韩欧美一区,四虎永久免费黄色影片,亚洲精品丝袜久久久久久 http://www.whjsdny.com Fri, 02 Feb 2024 02:52:20 +0000 en hourly 1 http://wordpress.org/?v=3.1 3 dB原則(法則) – DTX-1800/DSX2-8000 CableAnalyzer http://www.whjsdny.com/archives/3db-rule.html http://www.whjsdny.com/archives/3db-rule.html#comments Thu, 05 Jul 2018 08:12:39 +0000 深圳連訊 http://www.whjsdny.com/?p=10078 A YouTube video explaining how this this works is also?available from here.

This is applicable to ALL test limits in the DTX CableAnalyzer where a Return Loss measurement is made.

When?the Insertion Loss is less than 3.0 dB at the frequency point where the measurement is made, then the Return Loss measurement is ignored and not evaluated against the selected Test Limit/Cabling Standard in the DTX CableAnalyzer.This is often referred to as the?3 dB rule.It applies to ALL cabling standards/test limits in the DTX CableAnalyzer.

On a short?link,
the Insertion Loss may never reach 3.0 dB.If that were to happen, then the entire measurement would be?ignored, or as the cabling standards phrase it; “recorded for information only”.If this were to happen with your DTX CableAnalyzer, you would see an “i” appear next to the summary result for that test parameter.In LinkWare software, the result would be recorded with “N/A’.An example is shown below:

Concern is normally caused when the result has a negative margin.In this example we see the Return Loss margin was -2.2. A?negative margin is normally associated with a FAIL, but because the entire link never exceeded 3.0 dB Insertion Loss, it is not a FAIL.

Let’s review in detail how this works by looking at another example test result.

A TIA Cat 5e Perm.Link AUTOTEST was run on a 29.0 m installed link, giving the following result:

Looks normal – very nice margins.Let’s take a look at the Return Loss result in a little more detail:

You will observe that?the limit line has two colors, black and red.The cabling standards do not require the cable tester manufacturer to display where the?3 dB rule is implemented to the user, only that it is implemented.However, the DTX CableAnalyzer will indicate where the 3 dB rule has been implemented by changing the color of the limit line.If the?limit line is black, it?indicates that the Insertion Loss was less than 3.0 dB.If the?limit line is red, the Insertion Loss was 3.0 dB or greater.So for this Pair 3,6 the Return Loss?is not evaluated below 29.3 MHz. Let’s take a quick look at the Insertion Loss for Pair 3,6:

As you can see, the Insertion Loss reached 3.0 dB at 29.3 MHz, as previously indicated in the Return Loss Pair 3,6 graph above.

It’s an interesting rule, because if it were not in place, our margin for the above result would reduce from 10.2 dB to 9.0 dB:

As previously mentioned, if the link is particularly short, then the Insertion Loss may never reach 3.0 dB and the entire Return Loss?result is “ignored”.Let’s take a closer look at the first example where the test result was:

Looking at the worst case Return Loss result, we see the entire limit line is black, suggesting that the Insertion Loss for Pair?3,6 never reached 3.0 dB:

Looking at the Insertion Loss for Pair 3,6:

We see that the Insertion did indeed never reach 3.0 dB, so the entire measurement is not evaluated against the limit line (ignored) and recorded as “i” Information Only.If this result was downloaded to LinkWare Software, the report would show N/A against this measurement:

No further action is required by the installer.This is a valid standards compliant result.

 

]]>
http://www.whjsdny.com/archives/3db-rule.html/feed 0
【3dB 原則】RL 通過?失敗? – 數據電纜測試入門和常見測試問題解答 http://www.whjsdny.com/archives/3db-rule-rl.html http://www.whjsdny.com/archives/3db-rule-rl.html#comments Fri, 08 Sep 2017 05:43:22 +0000 深圳連訊 http://www.whjsdny.com/?p=9254 【3dB 原則】RL 通過?失敗??如果一條鏈路測得的衰減值不大,這通常意味著這條鏈路不長,傳過來的信號較強。那么,此時即便回波信號較強,信噪比 S/N 也不會太低,接收端仍能很好地分辨出信號。所以,當你發現測試的回波損耗值超標但測試結果卻標示為“通過”時,就是 3dB 原則在起作用了(3dB 損耗大約對應 10-15 米線對長度)。國際標準 ISO11801 和 TIA568C 都對此做了規定。此規定偏向于布線產品供應商。簡單地說就是:鏈路短即便回波強也不怕。

]]>
http://www.whjsdny.com/archives/3db-rule-rl.html/feed 0
鏈路太短應小心近端串擾和回波損耗 http://www.whjsdny.com/archives/proximal-crosstalk-and-return-loss.html http://www.whjsdny.com/archives/proximal-crosstalk-and-return-loss.html#comments Wed, 08 Dec 2010 02:15:06 +0000 深圳連訊 http://www.whjsdny.com/?p=337 在普通建筑的綜合布線設計、施工、驗收中,長度往往是最為關注的問題。由于銅導體其固有的電阻屬性導致銅纜的傳輸距離不可能太長,為此TIA組織制訂了最長90米的鏈路、最長100米的通道標準,更多的人關注的是能不能把銅纜的傳輸距離傳播的更遠一些。

幾乎很少有人關注短鏈路問題。眾所周知,銅纜長度越長,測試的參數越低,性能越差。短鏈路問題是指鏈路越短時,測試的參數越低,通過測試的可能性越低。尤其是鏈路長度低于15米時,近端串擾NEXT)和回波損耗(RL)這兩個重要的參數性能急劇下降。根據TIA/EIA標準,把“短鏈路”定義為連接器之間小于或等于15米的水平電纜鏈路。短鏈路問題則定義為當兩個連接器之間的水平電纜距離足夠短于標準時,第二個連接器的NEXT和回波損耗效應沒有被完全衰減

在信號傳輸過程中,信號碰到特性阻抗不連續的地方(端接模塊、線纜扭曲擠壓),會有較強的反射信號回來。如果鏈路較短,強烈的反射信號得不到足夠的衰減,在信號發送端就會檢測到較強的回波信號,大的反射信號可能會被看成接收的信號,這種效應會產生誤碼,測試也就會造成回波損耗測試失敗。就像粗水管的水進入細水管時,水流會倒回。標準委員會注意到了此現象,在TIA組織發布了568B六類布線標準之后,緊接著發布了TIA 568B.2-3。在附錄中對短鏈路的插入損耗、回波損耗的判斷做了修訂,引入3dB原則。當被測的鏈路插入損耗小于3dB時,回波損耗性能可以忽略,不作為判斷鏈路總體性能的通過與否的依據。

近端串擾(NEXT)是另外一個比較重要的參數,它是接收的正確信號與近端串擾信號之間的一個比值。在信號傳輸過程中,高頻率的電子時鐘使得信號之間的互相干擾比較強烈。如果在施工過程中出現開絞距離過大時,就會造成近端串擾測試不通過現象。在短鏈路中遠端產生的NEXT信號沒有經過有效的衰減,傳達到近端,導致測試結果失敗。ISO組織在ISO11801標準中,引入4dB原則,即當被測的鏈路插入損耗小于4dB時,NEXT性能可以忽略,不作為判定鏈路總體性能通過與否的依據。該原則僅適合于ISO標準,不適合于TIA標準。

普通建筑內部的短鏈路較少但是數據中心機房的布線系統短鏈路居多,可見短鏈路問題和長鏈路問題同樣值得關注。可以通過以下措施解決短鏈路問題:

1、避免發生在設計和施工過程中,盡量減少短鏈路現象的發生,盡量使鏈路長度長于15米但是并不推薦無謂的增加鏈路長度。

2、保證施工過程中不出現線纜過度扭曲,拒絕野蠻施工

3、良好的模塊、配線架端接。

4、在施工過程中,及時發現 ,盡早解決。

]]>
http://www.whjsdny.com/archives/proximal-crosstalk-and-return-loss.html/feed 0
主站蜘蛛池模板: 清水河县| 尚义县| 八宿县| 屯门区| 离岛区| 阳江市| 万载县| 象州县| 贵州省| 高邑县| 扶绥县| 金川县| 利川市| 略阳县| 威信县| 郴州市| 湟源县| 射阳县| 司法| 扬中市| 达尔| 夹江县| 新和县| 囊谦县| 鄂州市| 玛纳斯县| 噶尔县| 遂溪县| 堆龙德庆县| 资阳市| 潞城市| 高州市| 沁源县| 张家界市| 永年县| 青岛市| 鹰潭市| 仙桃市| 舟曲县| 大兴区| 京山县| 格尔木市| 青龙| 泽库县| 集安市| 观塘区| 金门县| 正镶白旗| 永康市| 桃源县| 兴义市| 平利县| 乐至县| 扶沟县| 舟山市| 贵港市| 新丰县| 罗田县| 乌鲁木齐市| 会同县| 阿鲁科尔沁旗| 巩义市| 大方县| 海阳市| 鹿泉市| 宜兰县| 东乡县| 原阳县| 卓尼县| 叙永县| 漳浦县| 康保县| 湘乡市| 金山区| 兴海县| 东辽县| 林周县| 迁安市| 昆山市| 崇礼县| 凤冈县| 教育|