在ANSI/TIA、ISO/IEC和IEEE中發現的插入損耗限制是基于在20℃(68μF)下運行的鏈路。隨著溫度的升高,你可以預期你的鏈接的插入損耗也會增加。在設計中沒有考慮到這一點可能會導致傳輸錯誤。在某些情況下,預期的應用可能不起作用。
布線標準為這一主題提供了極好的指導。
ANSI/TIA568C.2附錄G
電纜可以安裝在天花板空氣空間、提升管軸和非空調建筑如倉庫和制造工廠中,其中溫度可以顯著高于20℃,以確保符合CLAU規定的通道插入損耗。SE 62.7,根據電纜長度上的環境平均溫度、安裝電纜的插入損耗裕度和電纜的插入損耗溫度系數,水平電纜距離可能需要降低到90米以下。
ISO/IEC 11801:2011表32——水平溝道長度方程
對于高于20℃的工作溫度,對于屏蔽電纜,H應減少0.2%,每C C減少0.4%,每C C(20℃至40℃),未屏蔽電纜的0%,6%C(>40℃~60℃)。其中H是長度。
該ANSI/TIA568C.2標準繼續以表格的形式提供額外的指導:
The Insertion Loss limits found in ANSI/TIA, ISO/IEC and IEEE are based on the link operating at 20 ?C (68 ?F). As temperature increases, you can expect the Insertion Loss of your link to increase too. Failing to take this into account in your design may result in transmission errors. In some cases, the intended application may not work.
The cabling standards provide excellent guidance on this subject. You are encouraged to purchase these online at either?https://global.ihs.com or?http://www.iso.org.
ANSI/TIA-568-C.2 Annex G
Cables may be installed in return air plenums, in ceiling spaces, riser shafts and non air-conditioned buildings such as warehouses and manufacturing plants where the temperature can be significantly higher than 20 ?C. In order to ensure compliance with the channel insertion loss specified in clause 6.2.7, the horizontal cable distance may need to be reduced below 90 meters depending upon the average temperature of the environment over the length of the cable, the insertion loss margin of the installed cabling, and the insertion loss temperature coefficient of the cable.
ISO/IEC 11801:2011 Table 32 – Horizontal channel length equations
For operating temperatures above 20 ?C, H should be reduced by 0,2 % per ?C for screened cables; 0,4 % per ?C (20 ?C to 40 ?C) and 0,6 % per ?C (>40 ?C to 60 ?C) for unscreened cables. Where H is length.
This ANSI/TIA-568-C.2 standard goes on to provide additional guidance in the form of a table:
|
Temperature (?C?(?F)) |
Maximum
horizontal?unscreened cable?length?(m) |
Maximum
horizontal screened cablelength?(m) |
Length?de-rating?(m) (unscreened) |
Length?de-rating?(m)(screened) |
| 20?(68)
25?(77) 30?(86) 35?(95) 40?(104) 45?(113) 50?(122) 55?(131) 60?(140) |
90.0
89.0 87.0 85.5 84.0 81.7 79.5 77.2 75.0 |
90.0
89.5 88.5 87.7 87.0 86.5 85.5 84.7 83.0 |
0.0
1.0 3.0 4.5 6.0 8.3 10.5 12.8 15.0 |
0.0
0.5 1.5 2.3 3.0 3.5 4.5 5.3 6.0 |
Some field testers allow you to adjust the insertion loss PASS/FAIL line based on temperature. This is not permitted per ANSI/TIA, ISO/IEC and IEEE. If your cable is to be subjected to an elevated temperature, your design must take this into account by reducing the length of the link, not by relaxing the Insertion Loss limit.
Fluke Networks DSX-5000或者DSX-5000? does not allow you to adjust the Insertion Loss in any of its field testers based on temperature.
本文關鍵字: DSX-5000, Fluke, 插入損耗, 福祿克, 衰減
原創標題:福祿克DSX-5000:溫度對應福祿克插入損耗(衰減)測試的影響
原文鏈接:http://www.whjsdny.com/archives/dsx-il-temp.html
版權說明:本文為深圳市連訊達電子技術開發有限公司官網(www.whjsdny.com)版權所有。如果您需要轉載,請注明出處并保留原文鏈接!如為轉載文章會注明文章出處,轉載文章不代表本公司觀點。對于某些同行無恥惡意抄襲剽竊連訊客戶案例的違法行為,連訊將追究法律責任!
詳情請致電連訊公司:0755-83999818



新一代中文手持式測試儀 – 省時省力。
新一代中文手持式測試儀 – 省時省力。
新一代手持式網絡分析儀 – 省時省力。
新一代快速OTDR測試儀 – 省時省力。